Honeywell Flame Amplifier R7861A1034
- Extended Product Type : Other
-
- Product ID : R7861A1034
- Honeywell Type Designation : Other
Features
- Flame failure response time of 0.8 or 3.0 seconds.
- Flame signal strength ranges from 0.0 to 5.0 Vdc.
- Plug into 7800 relay module through printed circuit board edge connector keyed for proper orientation.
- Flame signal test jacks to measure amplifier flame signal voltage.
- Color-coded labels identify flame detection type. Dynamic Self-Check Amplifier test the detectors and all electronic components in the flame detection system 7800 SERIES relay module locks out on safety shutdown with flame detection system failure.
- Compatible with existing Honeywell flame detectors (order separately).
Specification of Honeywell R7861A1034
- Flame Failure Response Time (sec) : 0.8 sec or 1.0 sec
- Use With Primary Safety Control : 7800 SERIES Relay Modules
- Use With Flame Sensor : Gas, oil, coal: Ultraviolet Flame Sensor C7061